Diagnosing Power Problems
at the Receptacle:
Three quick measurements can tell you a great
deal
By measuring hot-neutral voltage, neutral-ground voltage
and hot-ground voltage you are well on your way to answering
these questions:
Is the outlet wired incorrectly?
Is the branch circuit too heavily loaded?
Do sensitive electronic loads have the voltage they need?
These three measurements, all taken quickly at one outlet,
provide you with a solid understanding of the building’s
electrical supply.
Testing a three-slot receptacle for grounding polarity
Incorrectly wired receptacles are not uncommon. A three-slot
receptacle has a hot-slot (short), a neutral slot (long)
and a grounding slot (U-shaped). Are the hot (black) and
neutral (white) wires reversed? Are the neutral and ground
(green) wires reversed or shorted?
These conditions can go undetected for a long time. Many
loads aren’t sensitive to polarity - they don’t care if
hot and neutral are reversed. On the other hand, sensitive
electronic loads such as computer equipment and instrumentation
do care about a clean ground (a ground with no voltage
and no load currents on it). A single reversed neutral
and ground can compromise the entire ground system.
So what do you find?
Hot-neutral is the load voltage. Voltage should read about
120 V (typically 115 V to 125 V). You measure exactly
118.5 V.
Neutral-ground is a voltage drop (also called IR drop)
caused by load current flowing through the impedance of
the white wire. Let’s say you measure 1.5 V.
Hot-ground can be thought of as the source of voltage
available at the receptacle. You read 120.0 V. You note
that hot-ground is higher than hot-neutral. In fact, hot-ground
is equal to the sum of the hot-neutral and neutral-ground
voltages.
Are these readings normal?
Is the outlet wired correctly?
The most common mis-wiring occurs if hot and neutral are
switched, or if neutral and ground are either switched
or shorted. How do you spot these conditions?
1. Measuring hot-neutral by itself does not tell you if
they’ve been switched. You have to measure neutral-ground
or hot-ground. If neutral-ground voltage is about 120
V and hot-ground is a few volts or less, then hot and
neutral have been reversed.
2. Under load conditions, there should be some neutral-ground
voltage - 2 V or a little bit less is pretty typical.
If neutral-ground voltage is 0 V - again assuming that
there is load on the circuit - then check for a neutral-ground
connection in the receptacle, whether accidental or intentional.
3. To check if neutral and ground are switched, measure
hot-neutral and hot-ground under load. Hot-ground should
be greater than hot-neutral. The greater the load, the
more the difference. If hot-neutral voltage, measured
with load on the circuit, is greater than hot-ground,
then the neutral and ground are switched. This is a potential
safety hazard and the condition should be corrected immediately.
Hot-ground reading should be the highest of the three
readings. The ground circuit, under normal, non-fault
conditions, should have no current and therefore no IR
drop on it. You can think of the ground connection as
a wire running back to the source (the main panel or the
transformer), where it’s connected to the neutral. On
the receptacle end of the ground path, where the measurement
is being made, the ground is not connected to any voltage
source (again, assuming there is not a fault). So the
ground wire is like a long test lead back to the source
voltage. When there is a load connected, the hot-ground
receptacle source voltage should be the sum of the hot-neutral
voltage (the voltage across the load) and the neutral-ground
voltage (the voltage drop on the neutral all the way back
to its connection to the ground circuit).
|